APPROVAL      
Test standard IEC/EN61984£º2009 / UL1059    
Pitch[mm] 7.62    
Poles 2-16P    
EN61984 Test data /    
Rated voltage[V] 400    
Rated current[A] 20    
Rated connection capacity(solid/stranded) [mm²] 2.5    
Surge voltage category/pollution degree/material group ¢ó/2/I    
Rated impulse voltage[KV] 2.5    
Rated torque[N·m] 0.4    
UL1059Test data UL File Number E228872    
Use group B C D
Rated voltage[V] 300 / 300
Rated current[A] 15 / 10
Rated connection capacity(solid/stranded) [AWG] 28-Dec    
Rated torque[Lb. in] 3.54    
General data /    
Screw M2.5      
Inflammability class UL94 V-0    
Ambient temperature[¡æ] -40~+105    
Relative humidity 5%-95%    
Inspection standard MIL-STD-105E II    
AQL 0.65    
Warranty 12 months    
Material and plating /    
Housing PA66    
Screws Steel£¬Zn plated    
Contact
Copper alloy£¬Sn plated    
Cage Copper alloy£¬Ni plated    
Wire connecting      
Recommended stripping length 7-8mm;      
For solid wire, stripping wire to the appointed length, then tightening with rated torque.    
For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque.
Tightening process should be steady, can’t use explosive force.    
 