Mobicon-Remote Electronic Pte Ltd
50 Ubi Ave 3,
#02-06 Frontier,
Singapore 408866.
+65-67477472
+65-67476768

DEGSON 15EDGK-5.08 PLUGGABLE TERMINAL BLOCK

Previous 73 / 334 Next

DEGSON 15EDGK-5.08 PLUGGABLE TERMINAL BLOCK Pluggable Terminal Block Terminal Blocks Degson
Quantity
Add Quotation


Item Data    
APPROVAL      
Test standard IEC/EN61984£º2009 / UL1059    
Pitch[mm²] 5.08    
Poles 02-12P    
EN61984 Test data VDE certificate NO. 40025627    
Rated voltage[V] 450    
Rated current[A] 7    
Rated connection capacity(solid/stranded) [mm²] 0.5~1.5    
Surge voltage category/pollution degree/material group II/2/II    
Rated impulse voltage[KV] 4    
Rated torque[N·m] 0.2    
UL1059Test data UL File Number E228872    
Use group B C D
Rated voltage[V] 300 / 300
Rated current[A] 8 / 8
Rated connection capacity (solid/stranded) [AWG] 28-16    
Rated torque[Lb. in] 1.77    
General data /    
Screw M2    
Inflammability class UL94 V-0    
Ambient temperature[¡æ] -40~+105    
Relative humidity 5%-95%    
Inspection standard MIL-STD-105E II    
AQL 0.65    
Warranty 12 months    
Material and plating /    
Housing PA66    
Screws Steel£¬Zn plated    
Contact Copper alloy£¬Sn plated    
Cage Copper alloy£¬Ni plated    
Wire connecting      
 Recommended stripping length 6-7mm;      
For solid wire, stripping wire to the appointed length, then tightening with rated torque.    
For stranded wire: stripping wire to the appointed length, mating with corresponding type of ferrule, then tightening with rated torque.
Tightening process should be steady, can’t use explosive force.  


You have 0 items in you cart. Would you like to checkout now?
0 items
Switch to Mobile Version
Recent Updates
Subscribe Newsletter
1
Hello! Thanks for visiting my site. Please press Start button to Contact with Admin :)

Start